SPEED ERROR TRIP FAULT
Otis · DSD 412 DC Elevator Drive
Hva betyr 410 ?
A large speed error existed for a significant period of time. Speed errors larger than Function #100, for longer than Function #99 seconds, will cause a Speed Error Trip and automatic drive shutdown.
Vanlige årsaker
- Dragging elevator brake.
- Weak motor field.
- Speed error magnitude exceeded Function #100 (Speed Error Trip Threshold).
- Speed error duration exceeded Function #99 (Speed Error Trip Time).
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check for a dragging brake.
- 2
Check the motor field strength.
- 3
Review Function #99 (Speed Error Trip Time) to adjust time sensitivity (range 0.20 – 5.00 seconds).
- 4
Review Function #100 (Speed Error Trip Threshold) to adjust magnitude sensitivity (range 0.0 – 100.0%).