00130000 hex

Main Memory Check Error

Omron · NX-series CPU Unit

Hva betyr 00130000 hex ?

An error was detected in the memory check of the main memory in the CPU Unit's PLC Function Module. This error is continuously detected, indicating a major fault level, and will stop user program execution and controller operation.

Vanlige årsaker

  • A conductive material has gotten inside the CPU Unit.
  • Noise causing data corruption in memory, microcomputer malfunctioning, or memory write circuit malfunctioning.
  • A software error.
  • Data corruption caused by cosmic rays or radiation.
  • CPU Unit hardware failure (memory element failure, memory peripheral circuit failure).

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    If conductive material is suspected, blow out the CPU Unit with air.

  2. 2

    Ensure the control panel is closed during operation and avoid metal working nearby.

  3. 3

    If noise is suspected, check the FG (Frame Ground) and power supply lines, then implement noise countermeasures.

  4. 4

    Cycle the power to the Controller; if the error persists or occurs frequently, replace the CPU Unit.

  5. 5

    Perform regular inspections of the CPU Unit's memory and peripheral circuits.