000D0000 hex

Internal Bus Check Error

Omron · NX-series CPU Unit

Hva betyr 000D0000 hex ?

A fatal error was detected on the internal bus of the PLC Function Module. This issue is continuously monitored and indicates potential hardware failure or interference. If this error occurs, the user program and CPU Unit operation will stop, and connection to the Sysmac Studio may not be possible. A power cycle is required for recovery.

Vanlige årsaker

  • Conductive material has entered the CPU Unit or surrounding area.
  • Noise interference causing data corruption in bus signals or malfunctioning bus interface circuits.
  • Internal bus disconnection or other hardware failure within the CPU Unit.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    If conductive material is nearby, blow out the CPU Unit with air.

  2. 2

    Ensure no metal working is performed near the control panel, and the operating environment is free of dirt and dust. Confirm the control panel is closed.

  3. 3

    If the error persists after cleaning, check the FG (Frame Ground) and power supply lines, along with other noise entry paths, and implement appropriate noise countermeasures.

  4. 4

    If the error continues after noise countermeasures, replace the CPU Unit.

Se alle koder i denne manualen (17)
Verifisert teknisk data. Sist oppdatert: March 2026