UP

Compressor overcurrent interruption

Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit

Hva betyr UP ?

Compressor overcurrent is detected after 30 seconds of compressor operation, indicating an excessive current draw. Potential causes include a closed stop valve, insufficient power supply voltage, incorrect compressor wiring, fan malfunctions, short cycling, or a defective compressor or outdoor controller board input circuit. This fault protects the compressor from immediate damage but requires prompt resolution to prevent component failure.

Vanlige årsaker

  • Refrigerant overcharge or non-condensable gases causing excessively high discharge pressure and compressor workload.
  • Insufficient heat transfer at the condenser (e.g., blocked fins, fan failure) leading to high head pressure and increased current draw.
  • Contamination or degradation of the compressor lubricating oil, increasing internal friction and motor load.
  • Faulty internal motor windings (e.g., winding short-to-ground, inter-turn short) leading to excessive current draw.
  • Unbalanced supply voltage phases (e.g., >2% deviation) causing stress and increased current in one or more compressor windings.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Connect a manifold gauge set to monitor suction and discharge pressures, verifying they are within operating limits.

  2. 2

    Measure the current draw on each phase of the compressor motor (e.g., L1, L2, L3) using a clamp-on ammeter and compare to nameplate RLA.

  3. 3

    Verify the supply voltage at the compressor terminals (e.g., T1, T2, T3) for phase balance and nominal voltage levels.

  4. 4

    Inspect the condenser coils for cleanliness and confirm the outdoor fan is operating effectively to reject heat.

  5. 5

    Perform an oil analysis (if accessible) to check for contaminants or degradation in the compressor lubricating oil.

Se alle koder i denne manualen (45)
Verifisert teknisk data. Sist oppdatert: March 2026