Oversetter...
02

Undervoltage Error

Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit

Hva betyr 02 ?

The power circuit board has detected an undervoltage condition in the input power supply. This can lead to improper operation, instability, or failure of the system's components, particularly the compressor, due to insufficient power.

Vanlige årsaker

  • Input voltage to the unit is below the normal operating range.
  • Voltage sag or brownout from the electrical grid.
  • Faulty power supply.
  • Loose electrical connections.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure the input power supply voltage at the main terminals to verify the actual voltage level.

  2. 2

    Check the external power supply for stability and correct voltage output.

  3. 3

    Inspect the power circuit board for any visible damage or component failure.

Se alle koder i denne manualen (45)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Mitsubishi Electric PUZ-HA30/36NHA4 Outdoor Unit