Oversetter...
U6

Power Module Abnormality

Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit

Hva betyr U6 ?

An abnormality is detected in the power module, often signaled by overcurrent during module operation (which can trigger UF or UP errors). This critical fault can be caused by a closed outdoor stop valve, low power supply voltage, incorrect or loose compressor wiring, or a defective compressor or outdoor power circuit board.

Vanlige årsaker

  • Power module failure or internal short circuit.
  • DC bus voltage abnormal.
  • Control board communication error with power module.
  • Overcurrent or overvoltage protection triggered within the power module.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify that the outdoor stop valve is fully open.

  2. 2

    Check the facility's power supply voltage to ensure it meets the system specifications.

  3. 3

    Correct the wiring (U, V, W phase) to the compressor if any connections are loose, disconnected, or conversed.

  4. 4

    Check the compressor for defects, referring to diagnostic procedures in section 10-6 of the manual.

  5. 5

    If the above steps do not resolve the issue, replace the outdoor power circuit board.

Se alle koder i denne manualen (45)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Mitsubishi Electric PUZ-HA30/36NHA4 Outdoor Unit