IO-STATUS-LED-OFF

I/O Status LED Off (Input)

Mitsubishi Electric · MELSEC iQ-R I/O Module

Hva betyr IO-STATUS-LED-OFF ?

The I/O status indicator LED for a specific input point is not illuminated, suggesting that the external input signal is either not present, not strong enough, or not being processed correctly by the I/O module. This can be due to a missing or incorrect external power supply to the I/O module or an internal module failure.

Vanlige årsaker

  • External power supply to the I/O module is not provided or does not meet the specified voltage requirements.
  • The physical state of the input device does not correspond to the I/O indicator LED, potentially due to wiring issues.
  • Internal failure of the I/O module preventing correct input signal detection.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify that the external power supply for the I/O module is connected and that its voltage meets the module's specifications.

  2. 2

    Use the engineering tool to perform a forced ON/OFF operation on the device concerned and observe if the I/O indicator LED responds accordingly.

  3. 3

    If the I/O indicator LED error persists after troubleshooting, consult your local Mitsubishi Electric representative.