1100H

Transmission Interval Monitoring Time Range Error

Mitsubishi Electric · MELSEC iQ-R I/O Module

Hva betyr 1100H ?

A value outside the permissible range of 6 to 3000 has been configured for the 'Transmission interval monitoring time' parameter. This incorrect setting prevents the module from operating correctly, as it relies on a valid monitoring interval.

Vanlige årsaker

  • The 'Transmission interval monitoring time' parameter is set to a value less than 6.
  • The 'Transmission interval monitoring time' parameter is set to a value greater than 3000.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Set the 'Transmission interval monitoring time' parameter within the valid range from 6 to 3000.

Se alle koder i denne manualen (56)