INPUT-SNEAK-PATH
Input Sneak Path Current (Multiple Power Supplies)
Mitsubishi Electric · MELSEC iQ-R I/O Module
Hva betyr INPUT-SNEAK-PATH ?
An input signal does not turn off due to a sneak path current created by the use of two power supplies in the system. This unintended current flow bypasses the intended circuit, keeping the input module falsely activated, especially when voltage E1 is greater than E2.
Vanlige årsaker
- Use of two power supplies in the input circuit where voltage differences (E1 > E2) create an unintended current path (sneak path).
- Incorrect wiring configuration leading to alternative current routes that keep the input signal active.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Consolidate the input circuit to use a single power supply to eliminate the conditions for a sneak path.
- 2
If two power supplies are absolutely necessary, connect a diode in series with the input device to block any reverse current flow and prevent the sneak path.