INPUT-LKG-C3

Input Leakage Current (Line Capacitance)

Mitsubishi Electric · MELSEC iQ-R I/O Module

Hva betyr INPUT-LKG-C3 ?

A leakage current flows into the input module due to the inherent capacitance of long wiring cables, preventing the input signal from turning off. This is particularly common with twisted pair cables, which can have a line capacity of approximately 100pF/m, contributing to unwanted current flow.

Vanlige årsaker

  • High line capacitance of excessively long wiring cables.
  • The accumulated charge in the cable capacitance creates a leakage current that maintains the input above the OFF voltage threshold.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Connect an appropriate resistor in parallel across the input terminals to sink the leakage current and ensure the voltage drops below the OFF threshold (same as INPUT-LKG-C1).

Se alle koder i denne manualen (56)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Mitsubishi Electric MELSEC iQ-R I/O Module