98 H
Output disconnection detection
Mitsubishi Electric · MELSEC iQ-R I/O Module
Hva betyr 98 H ?
A disconnection has been detected on an output terminal. This indicates a physical break in the wiring or loss of continuity to the connected output device, preventing the module from controlling the device.
Vanlige årsaker
- Physical disconnection of an output line or cable.
- Faulty connected load or actuator.
- Loose or damaged terminal connection at the output module or load.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Recover the connection to the output terminal by re-securing wiring or replacing the faulty output device.
- 2
After connection recovery, turn 'Alarm clear request' (Y11) on and off to clear the alarm.
- 3
Verify that 'Output disconnection detection status' reads 0 (Normal) and 'Alarm flag' (X11) turns off after clearing.