Oversetter...
88  H

Input disconnection detection

Mitsubishi Electric · MELSEC iQ-R I/O Module

Hva betyr 88  H ?

A disconnection has been detected on an input terminal. This indicates a physical break in the wiring or loss of signal from the connected input device, preventing proper signal reception by the I/O module.

Vanlige årsaker

  • Physical disconnection of an input line or cable.
  • Faulty input device failing to provide a signal.
  • Loose or damaged terminal connection at the input module or sensor.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Recover the connection to the input terminal by re-securing wiring or replacing the faulty input device.

  2. 2

    After connection recovery, turn 'Alarm clear request' (Y11) on and off to clear the alarm.

  3. 3

    Verify that 'Input disconnection detection status' reads 0 (Normal) and 'Alarm flag' (X11) turns off after clearing.

Se alle koder i denne manualen (56)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Mitsubishi Electric MELSEC iQ-R I/O Module