26105
Ground fault, KPP/KSP (axis)
Kuka · KR C4 Controller
Hva betyr 26105 ?
This fault indicates a power unit overcurrent condition specifically due to a ground fault on an axis. It points to an insulation breakdown or unintended conductive path to ground in the motor or its cabling, leading to excessive current flow.
Vanlige årsaker
- Insulation breakdown or damage in the motor cable, causing a short to ground.
- Internal ground fault within the motor windings or housing.
- Damaged components within the KPP or KSP causing a ground path.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Visually inspect the motor cable for insulation damage or signs of arcing.
- 2
Measure insulation resistance of the motor cable between phases and to ground using a megger.
- 3
Measure insulation resistance of the motor windings to ground.
- 4
Reinitialize the drive bus by performing a Power Off / Power On cycle.
- 5
Inspect KSP (KUKA SmartPAD) and KPP (KUKA Power Pack) for signs of damage or loose connections.