Ground fault, KPP/KSP (axis)

Kuka · KR C4 Controller

Hva betyr 26033 ?

This fault indicates a power unit overcurrent due to a ground fault in the motor or motor cable connected to a KPP/KSP drive. A ground fault poses a significant safety risk and can cause severe damage to electrical components.

Vanlige årsaker

  • Ground fault in the motor cable
  • Internal ground fault within the motor

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Inspect the motor cable for insulation breakdown or damage that could cause a ground fault.

  2. 2

    Check the motor for internal ground faults by measuring insulation resistance.

  3. 3

    Reinitialize the drive bus by cycling Power Off / Power On.

  4. 4

    Check the KSP module for any status indicators.

  5. 5

    Check the KPP module for any status indicators.