31 Pressure Sensor Fault

Kone · Elevator Control

Hva betyr 31 ?

A fault has been detected in Pressure Sensor 31, indicating an incorrect reading or circuit failure. This disables all motion functions.

Vanlige årsaker

  • Malfunction of Pressure Sensor 31 (e.g., open circuit, short circuit).
  • Damaged wiring or loose connections to Pressure Sensor 31.
  • Pressure reading outside of expected operational limits.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure supply voltage to Pressure Sensor 31 and verify it matches specifications.

  2. 2

    Inspect wiring and terminal connections for Pressure Sensor 31 from the sensor to the elevator control input module for damage, corrosion, or loose connections.

  3. 3

    Verify the output signal from Pressure Sensor 31 at the input module terminals, comparing against expected values (e.g., 4-20mA, 0-10V, or digital state).

  4. 4

    Check the Kone Elevator Control system's configuration parameters related to Pressure Sensor 31 for correct scaling, input type, and alarm thresholds.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026