DRIVER SHORTED
Kone · Elevator Control
Hva betyr 1074 ?
The motor controller (codes 1074, 2074, 3074) has detected a short circuit in a driver output stage. This typically indicates a fault in the power output section controlling a motor phase or internal component. The specific lift reaction is controller dependent.
Vanlige årsaker
- Short circuit on motor phase wiring (e.g., phase-to-phase, phase-to-ground).
- Motor winding insulation breakdown.
- Internal fault in the controller's power transistors (e.g., IGBT/MOSFETs).
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Inspect motor power cables for visible damage, chafing, or insulation breakdown from the controller to the motor.
- 2
Verify secure connections of motor power cables at both the motor controller output terminals and the motor terminal block.
- 3
Measure the insulation resistance of each motor phase winding to ground and between phases using an insulation tester.
- 4
Measure the resistance of each motor phase winding (U-V, V-W, W-U) with a multimeter and compare values for consistency.