Axis 2 Not Homed

Indramat · ServoDyn D Servo Drive

Hva betyr 36 ?

This error occurs if the user program attempts to execute an absolute position command for Axis 2, but Axis 2 has not yet been homed. Homing is essential to establish a precise absolute position reference.

Vanlige årsaker

  • Attempting to use absolute position commands for Axis 2 before a successful homing cycle has been performed.
  • Homing procedure for Axis 2 was initiated but not completed successfully due to an interruption or fault.
  • Incorrect configuration of homing parameters (Parameter 48, Homing Setup A2 and Parameter 49, Homing Offset A2) for Axis 2.
  • Faulty home limit switch or wiring preventing Axis 2 from detecting its home position.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify that Axis 2 parameters are correctly set for homing. Axis 2 can be homed in Manual or Automatic mode (refer to Chapter 4).

  2. 2

    Review the CLM01.3-M user program to ensure that absolute position commands for Axis 2 are only issued after Axis 2 has been homed.

  3. 3

    Perform the homing procedure for Axis 2 in either Manual or Automatic mode to establish a home reference.

  4. 4

    Inspect the home limit switch for Axis 2, including its wiring and mechanical actuation, to ensure it is functioning correctly.

  5. 5

    Check for any mechanical obstructions or binding that might prevent Axis 2 from reaching its home position during the homing cycle.