Min Travel Lmt 2

Indramat · ServoDyn D Servo Drive

Hva betyr 34 ?

This error occurs in Automatic mode for Axis 2 if the commanded position is smaller than the value configured in Parameter 51 (Minimum Travel Limit A2). The system detects an attempt to move Axis 2 beyond its defined minimum operational boundary.

Vanlige årsaker

  • The programmed command attempts to move Axis 2 below its Minimum Travel Limit set in Parameter 51.
  • Parameter 51 (Minimum Travel Limit A2) is set incorrectly or too high for the actual mechanical limits of Axis 2.
  • Overshoot of Axis 2 during deceleration, causing it to briefly exceed the minimum limit.
  • Incorrect position gain (Parameter 45) or tuning, leading to poor positioning accuracy for Axis 2.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify that the Axis 2 commanded position has exceeded the Axis 2 minimum travel limit.

  2. 2

    Ensure that Parameter 51 (Minimum Travel Limit A2) is correctly set to reflect the actual minimum mechanical travel limit for Axis 2.

  3. 3

    Adjust the user program to ensure that commanded positions for Axis 2 do not fall below the value specified in Parameter 51.

  4. 4

    If overshoot is occurring, optimize the position gain (Parameter 45) for Axis 2 to improve deceleration and stopping accuracy.

  5. 5

    Inspect the mechanical system for any binding or obstructions that could restrict movement or cause overtravel for Axis 2.