Oversetter...
10

Min Travel Lmt 1

Indramat · ServoDyn D Servo Drive

Hva betyr 10 ?

This error occurs in Automatic Mode for Axis 1 if the commanded position is smaller than the value configured in Parameter 11 (Minimum Travel Limit A1). The system detects an attempt to move Axis 1 beyond its defined minimum operational boundary.

Vanlige årsaker

  • The programmed command attempts to move Axis 1 below its Minimum Travel Limit set in Parameter 11.
  • Parameter 11 (Minimum Travel Limit A1) is set incorrectly or too high for the actual mechanical limits of Axis 1.
  • Overshoot of Axis 1 during deceleration, causing it to briefly exceed the minimum limit.
  • Incorrect position gain (Parameter 05) or tuning, leading to poor positioning accuracy.
  • Faulty encoder feedback for Axis 1 resulting in an inaccurate position reading.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify that Parameter 11 (Minimum Travel Limit A1) is correctly set to reflect the actual minimum mechanical travel limit for Axis 1.

  2. 2

    Adjust the user program to ensure that commanded positions for Axis 1 do not fall below the value specified in Parameter 11.

  3. 3

    If overshoot is occurring, optimize the position gain (Parameter 05) for Axis 1 to improve deceleration and stopping accuracy.

  4. 4

    Inspect the mechanical system for any binding or obstructions that could restrict movement or cause overtravel.

  5. 5

    Check for correct encoder operation and accurate position feedback from Axis 1.

Se alle koder i denne manualen (51)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Indramat ServoDyn D Servo Drive