Monitoring Safe Halt

Indramat · CLM01.3-M Flying Cutoff Control

Hva betyr F501 ?

The safety function Safe Halt is selected, but the drive interlock is not active, or the control has given the drive enable. This indicates a discrepancy in the safety circuit state, where the drive is enabled despite Safe Halt being active or the interlock being open.

Vanlige årsaker

  • Error in the actuation of the drive interlock (Indramat DIAX04 SSE-03VRS: connector X3).
  • Malfunction of the control system, sending an incorrect drive enable signal.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    De-energize the system. Inspect the wiring of the drive interlock circuit, specifically at the Indramat DIAX04 SSE-03VRS connector X3, for loose connections, damage, or incorrect termination.

  2. 2

    Verify the state of the drive interlock inputs to the Indramat DIAX04 SSE-03VRS drive controller using diagnostic tools or status indicators, ensuring they reflect the expected safety state (e.g., inactive when Safe Halt is selected).

  3. 3

    Check the status of the drive enable signal from the control system. Ensure that the control is not commanding drive enable while Safe Halt is active.

  4. 4

    Consult the control system's diagnostics and event logs for any errors or unexpected commands related to drive enable or safety functions.

  5. 5

    If the issue persists and appears to originate from the control system's logic or hardware, contact the control system manufacturer for further assistance.