Double MST failure shutdown
Indramat · CLM01.3-M Flying Cutoff Control
Hva betyr F401 ?
The master sync telegram (MST) was not received by the Indramat DIAX04 SSE-03VRS drive controller in two successive SERCOS cycles, indicating a communication breakdown in the SERCOS fiber optic ring.
Vanlige årsaker
- Disruption in the Fiber Optic transmission line.
- Too much attenuation of the light signal in the Fiber Optic cable.
- Malfunction in the SERCOS interface module of the drive controller (general).
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Visually inspect all Fiber Optic connections and cables in the SERCOS ring for physical damage, kinks, or improperly seated connectors. Ensure all connectors are clean.
- 2
Measure the optical power attenuation across each segment of the Fiber Optic cable using an appropriate optical power meter. Verify that the attenuation between TX and RX for any connection does not exceed 12.5 dB.
- 3
Check the status indicators (LEDs) on the SERCOS interface modules of all devices in the ring for any indications of link loss or communication errors.
- 4
If communication issues persist despite good cable integrity and attenuation, consider replacing the SERCOS interface module in the affected Indramat DIAX04 SSE-03VRS drive controller.