F382

Mains phase loss fault

Indramat · CLM01.3-M Flying Cutoff Control

Hva betyr F382 ?

With HVE power supply units only! At least one phase of the 3-phase power supply input to the HVE unit is missing, indicating a loss of input power similar to F381 but specific to HVE units.

Vanlige årsaker

  • At least one phase of the 3-phase power supply input to the HVE unit is missing.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the incoming 3-phase power supply at the input terminals of the Indramat HVE power supply unit using a multimeter. Confirm all three phases are present and balanced.

  2. 2

    Inspect all upstream mains fuses and circuit breakers for the power supply unit. Replace any blown fuses or reset tripped breakers.

  3. 3

    Check power contactors and their auxiliary contacts for proper operation and engagement in the power distribution circuit.

  4. 4

    Inspect all power wiring connections from the mains supply to the HVE unit for looseness, damage, or disconnections.