COUNT MISS(INT)

Fanuc · Series 0i-D/0i Mate-D Maintenance

Hva betyr 367 ?

This alarm on Fanuc Series 0i-D/0i Mate-D with αi/βi Pulsecoders indicates a position data count error from the built-in Pulsecoder. Root causes typically include Pulsecoder failure, electrical noise, or issues with signal transmission.

Vanlige årsaker

  • Internal failure of the Pulsecoder resulting in incorrect pulse counting.
  • Electrical noise causing corruption or loss of position data pulses.
  • Damaged or loose Pulsecoder cable leading to intermittent signal loss.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the integrity of the Pulsecoder cable, checking for physical damage, proper shielding, and secure connections at both ends.

  2. 2

    Investigate and mitigate any potential sources of electromagnetic interference (EMI) or noise affecting the Pulsecoder signal lines.

  3. 3

    Check the mechanical mounting of the Pulsecoder for looseness or vibration that could lead to intermittent counting errors.

  4. 4

    If noise mitigation, cabling, and mounting integrity are confirmed, replace the Pulsecoder unit.