ALARM 7

DC overvoltage

Danfoss · VLT HVAC Drive High Power

Hva betyr ALARM 7 ?

The DC-link voltage has exceeded its limit, causing the frequency converter to trip after a certain time. This often occurs due to regenerative braking or excessive mains voltage, which can damage the inverter section if not mitigated.

Vanlige årsaker

  • Excessively high incoming AC mains voltage, consistently above the frequency converter's maximum input voltage.
  • Rapid deceleration of a high inertia load, causing significant regenerative energy feedback to the DC link.
  • Braking resistor failure (open circuit) or incorrect sizing (too high resistance) if installed.
  • Deceleration ramp time (P3-42, P3-44) set too short for the application, generating excessive regenerative voltage.
  • Fault in the frequency converter's DC-link measurement or protection circuitry.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure the incoming AC mains voltage (L1-L2, L2-L3, L3-L1) and confirm it is within the frequency converter's specified operating range.

  2. 2

    Increase the deceleration ramp time (P3-42 for ramp 1, P3-44 for ramp 2) to allow for slower energy dissipation.

  3. 3

    Verify the connection and resistance of the external braking resistor (if present) and ensure it matches the value specified in P2-11 (Brake Resistor Ohms).

  4. 4

    Consider implementing a brake chopper and resistor combination or a regenerative front end for high inertia applications.

  5. 5

    Review the application for external forces causing motor regeneration, such as overhauling loads or rapid changes in load direction.