Oversetter...
17

Control word timeout

Danfoss · VLT HVAC Drive High Power

Hva betyr 17 ?

This warning/alarm indicates a loss of communication with the frequency converter. It becomes active when parameter 8-04 Control Word Timeout Function is not set to [0] Off. If configured to [2] Stop and [26] Trip, the frequency converter will ramp down and then trip into an alarm state, indicating a critical communication failure.

Vanlige årsaker

  • Loss of communication signal (e.g., Profibus, EtherNet/IP) from the master controller to the frequency converter.
  • Incorrect setting of parameter 8-04 Control Word Timeout Function, enabling detection of communication loss.
  • Physical cable break or poor connection in the communication bus wiring (e.g., RJ45 connector, M12 connector).
  • Master controller (PLC/DCS) stopped transmitting the control word or experienced an internal fault.
  • Communication module hardware failure on the frequency converter or master controller.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the status of the master controller (PLC/DCS) program execution and communication diagnostics.

  2. 2

    Check the status indicator LEDs on the frequency converter's communication module for communication activity and errors.

  3. 3

    Inspect the communication cable connections at both the frequency converter and the master controller for proper seating and damage.

  4. 4

    Measure continuity of communication cable pairs (e.g., EtherNet/IP RX/TX pairs) using a cable tester.

  5. 5

    Confirm parameter 8-04 Control Word Timeout Function is set to the desired value (e.g., [2] Stop or [1] Freeze output) for the application.

  6. 6

    If using a fieldbus, verify the network configuration (e.g., IP address, node ID, baud rate) matches the master controller settings.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Danfoss VLT HVAC Drive High Power