Oversetter...
49

Speed limit exceeded

Danfoss · VLT HVAC Drive High Power

Hva betyr 49 ?

The motor's actual speed is outside the range defined by parameter 4-11 (Motor Speed Low Limit [RPM]) and parameter 4-13 (Motor Speed High Limit [RPM]). If the speed drops below parameter 1-86 (Trip Speed Low [RPM]) (excluding start/stop conditions), the frequency converter will trip, indicating a potential control issue or an abnormal operating condition.

Vanlige årsaker

  • Actual motor speed exceeding parameter 4-13 Motor Speed High Limit [RPM] due to an incorrect speed reference or motor runaway.
  • Actual motor speed dropping below parameter 4-11 Motor Speed Low Limit [RPM] (and potentially below P1-86 Trip Speed Low Limit [RPM]) due to mechanical overload or stall.
  • Inaccurate speed feedback from encoder or tachometer (e.g., encoder cable noise, faulty sensor).
  • Incorrect configuration of speed limits (P4-11, P4-13) or trip speed low limit (P1-86) for the application.
  • Mechanical fault causing excessive friction or binding, leading to motor stall at low speeds.
  • Motor parameters (e.g., P1-20, P1-22, P1-25) incorrectly configured, leading to poor speed regulation.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Monitor the actual motor speed (e.g., LCP display P16-16 Actual Speed Filtered) and the speed reference (e.g., P16-15 Speed Reference) during operation.

  2. 2

    Verify parameters 4-11 Motor Speed Low Limit [RPM] and 4-13 Motor Speed High Limit [RPM] are set appropriately for the application's operating range.

  3. 3

    Check parameter 1-86 Trip Speed Low Limit [RPM] and ensure it is configured to prevent nuisance trips during normal low-speed operation.

  4. 4

    If an encoder is used, inspect encoder wiring (e.g., terminals 32, 33, 35, 36) for noise or damage and verify encoder pulses (e.g., P16-30).

  5. 5

    Check for any mechanical binding or excessive load on the motor that would cause it to stall or exceed its speed limits.

  6. 6

    Perform an Automatic Motor Adaptation (AMA) via parameter 8-10 to ensure motor parameters (e.g., P1-20, P1-22) are correctly identified and configured.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Danfoss VLT HVAC Drive High Power