CoF

Current Offset Fault

Yaskawa · GA500 Maintenance and Troubleshooting

¿Qué significa CoF ?

A Current Offset Fault occurs when the drive attempts to start operation while residual induced voltage is still present in the motor, such as after coasting to a stop or rapid deceleration. This indicates the current offset value has exceeded its permitted automatic adjustment range. In rare cases, this fault may also point to an internal hardware problem within the drive itself. Failure to resolve this can lead to incorrect motor control, erratic startup behavior, or potential damage if a hardware issue is present.

Causas comunes

  • Motor current offset detected is outside acceptable limits (P7-01).
  • DC offset in motor phase currents.
  • Faulty current sensor (CT).
  • Improper motor phase insulation.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Modify the control sequence to prevent restarting operation when induced voltage remains in the motor.

  2. 2

    Set b3-01 = 1 [Speed Search at Start Selection = Enabled] or use external Speed Search commands (H1-xx = 61, 62) to safely re-engage with a spinning motor.

  3. 3

    If the above steps do not resolve the fault and a drive hardware problem is suspected after initial troubleshooting, replace the drive. Perform a Fault Reset.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Yaskawa GA500 Maintenance and Troubleshooting