Traduciendo...
59
Follower Communication Fault
Vacon · NX All-in-One Application
¿Qué significa 59 ?
Communication between the Master and Follower drives has been lost via SystemBus or CAN. This indicates a broken communication link, preventing coordinated operation between the units.
Causas comunes
- Communication failure between a master and a follower drive/device.
- Incorrect follower address or configuration (e.g., P9-01).
- Network cabling issue between devices.
- Follower device powered off or not initialized.
- Data corruption during follower communication.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Verify the option board parameters related to SystemBus or CAN communication for correct configuration (e.g., node ID, baud rate).
- 2
Inspect the optical fibre cable or CAN cable for physical damage, proper connections, and correct termination between master and follower drives.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Vacon NX All-in-One Application