10
Input line supervision
Vacon · NX All-in-One Application
¿Qué significa 10 ?
An input line phase is missing, indicating a loss of one or more phases in the AC supply to the drive. This could be due to an open circuit in the supply cabling, a blown fuse, or a power distribution issue. Operating with a missing phase can damage the drive's input rectifier.
Causas comunes
- Input AC power phase is missing or unbalanced.
- Faulty input power rectifier or smoothing circuit.
- Loose connection on the AC input terminals.
- External power source fluctuation.
- Overload on the input stages.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure the phase-to-phase and phase-to-neutral supply voltages at the drive's input terminals — verify all phases are present and balanced.
- 2
Inspect all input fuses for continuity and ensure they are of the correct type and rating.
- 3
Physically check the supply cables connecting to the drive for any signs of damage, loose connections, or disconnections at the terminal block.
Datos técnicos verificados. Última actualización: March 2026