Earth Fault
Vacon · NX All-in-One Application
¿Qué significa 3 ?
The drive's current measurement system has detected that the sum of the motor phase currents is not zero, indicating a leakage current to earth. This is typically caused by an insulation malfunction in the motor cables or within the motor windings itself, posing a risk of electrical shock or further equipment damage.
Causas comunes
- Current leakage to chassis or ground detected.
- Insulation failure in motor windings or power circuitry.
- Faulty grounding connection.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Inspect the motor cables for any signs of damage, compromised insulation, or moisture ingress.
- 2
Perform an insulation resistance test (megger test) on the motor windings and cables to earth, and between phases, to identify insulation breakdowns.