06
Phase failure
SEW Eurodrive · [PDF] Operating Instructions
¿Qué significa 06 ?
The drive has detected a missing phase in the supply system leads. This fault is typically only detectable when the drive is operating under load, indicating an imbalance or complete loss of one or more input phases. Continued operation with a phase failure can lead to damage in both the motor and the inverter.
Causas comunes
- One or more phases are missing in the supply system lead.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the supply system lead for phase failure by measuring phase-to-phase voltages at the inverter input using a multimeter.
- 2
Reset the fault by switching off the DC 24 V supply voltage to the inverter for at least 10 seconds.
Datos técnicos verificados. Última actualización: March 2026