Traduciendo...
SLF

Modbus Fault

Schneider Electric · Altivar 312 Variable Frequency Drive

¿Qué significa SLF ?

This fault signals an interruption in communication on the Modbus bus, preventing the drive from exchanging data with a Modbus master or remote display terminal. Causes often include physical bus issues or a disconnected remote display terminal when HMI command is enabled. This results in a loss of external control, monitoring, or parameter access.

Causas comunes

  • Broken, disconnected, or improperly wired RS-485 Modbus communication cable (e.g., A/B lines reversed or open).
  • Incorrect Modbus slave address (Parameter P5-01) or baud rate (Parameter P5-02) configured in the drive or Modbus master.
  • Missing or incorrectly placed 120 Ohm termination resistors at the physical ends of the Modbus bus segment.
  • Excessive electrical noise or electromagnetic interference (EMI) on the communication lines, corrupting data packets.
  • Modbus master controller experiencing a communication timeout or not actively polling the drive.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Inspect the RS-485 Modbus communication cable for physical damage, loose connections, or incorrect wiring (e.g., A to A, B to B) at both the drive and master ends.

  2. 2

    2. Verify that the drive's Modbus slave address (Parameter P5-01) and baud rate (Parameter P5-02) match the configuration settings in the Modbus master controller.

  3. 3

    3. Check for the correct installation of 120 Ohm termination resistors at the two furthest physical ends of the Modbus bus segment.

  4. 4

    4. Measure the voltage differential between the Modbus A and B lines (should fluctuate between 0-5VDC during communication) using an oscilloscope or specialized Modbus tester.

  5. 5

    5. Ensure that no other device on the Modbus network is using the same slave address as the drive, causing address conflicts.

Ver todos los códigos en este manual (31)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Schneider Electric Altivar 312 Variable Frequency Drive