Traduciendo...
3

Network Status: Partial network fault

Phoenix Contact · FL SWITCH 7000

¿Qué significa 3 ?

A localized issue has been detected within a segment of the Device Level Ring (DLR). While the entire ring may still be operational, this indicates that a portion of the network is experiencing a problem, potentially affecting communication for specific nodes.

Causas comunes

  • Intermittent connection issues on a specific cable segment or DLR port.
  • A degraded cable segment that experiences high error rates without a complete break.
  • A single device within the ring experiencing a minor fault that doesn't fully disrupt the ring's integrity but degrades performance.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Use the "Verify Fault Location" button on the "DLR Status Information" web page (Figure 4-34) to pinpoint the affected segment by checking the IP addresses of "Last Node Port 1" and "Last Node Port 2".

  2. 2

    Inspect all DLR cables and connectors within the identified segment for any signs of physical damage, loose connections, or environmental stressors.

  3. 3

    Review the diagnostic logs of devices within the affected segment for any specific error messages or port status changes.

Ver todos los códigos en este manual (4)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Phoenix Contact FL SWITCH 7000