>1LS + 2LS !

Both 1LS and 2LS Operated

Otis · GAA21750AK3 Service Tool

¿Qué significa >1LS + 2LS ! ?

This blinking event message indicates that both Limit Switch 1 (1LS) and Limit Switch 2 (2LS) are simultaneously in an operated state, blocking elevator movement. This condition is typically indicative of an abnormal car position or a wiring fault within the OTIS 2000 Controllers MCS120/MCS220 system.

Causas comunes

  • Incorrect car positioning leading to simultaneous actuation of both limit switches.
  • Short circuit or cross-wiring in the limit switch circuits.
  • Mechanical fault causing both switches to remain in an operated state.
  • Faulty individual limit switches, causing one or both to be stuck in an actuated position.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the elevator car's actual position relative to the limit switches 1LS and 2LS.

  2. 2

    Inspect 1LS and 2LS for physical damage or simultaneous mechanical actuation.

  3. 3

    Check wiring for 1LS and 2LS circuits for short circuits or incorrect connections.

  4. 4

    Measure the individual state of each limit switch contact to identify if one is stuck in an operated position.

Ver todos los códigos en este manual (15)