Traduciendo...
F910

BLOWN FUSE

Otis · DSD 412 Elevator System

¿Qué significa F910 ?

This fault is detected by the PCU Diagnostics function (Function #998) and indicates that one or more AC line fuses are open within the DSD 412 drive power conversion unit.

Causas comunes

  • An AC line fuse has blown due to overcurrent or other electrical anomaly.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Remove power from the drive.

  2. 2

    Inspect and replace the identified blown AC fuse(s).

  3. 3

    Repeat the PCU Diagnostics function to confirm the issue is resolved.

Ver todos los códigos en este manual (57)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas