117/118
SERIAL COMMUNICATION FAULT
Otis · DSD 412 Elevator System
¿Qué significa 117/118 ?
Code 117 indicates serial communication did not start within 10 seconds after drive reset or power-up. Code 118 indicates a valid serial communication message was not received for more than 150 ms.
Causas comunes
- Host not connected or not sending valid messages.
- Electrical grounding noise interference.
- Parameter #110 set to selection 3 when serial communication is not being used.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Ensure the host is connected and sending valid messages.
- 2
Identify and correct electrical grounding noise interference problems.
- 3
If serial communication is not being used, verify parameter #110 is NOT set to selection 3.