97

OVERSPEED FAULT

Otis · DSD 412 Elevator System

¿Qué significa 97 ?

The motor speed has exceeded the trip level set in parameter #12, as measured by the encoder. Parameter #12 defines a percentage of the motor speed value set in parameter #11.

Causas comunes

  • Incorrect setting of parameters #10, #11, or #12.
  • Poor speed regulator tuning.
  • Velocity reference set above rated speed.
  • Intermittent velocity encoder operation.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check parameters #10, #11, and #12 for correct settings.

  2. 2

    Check speed regulator tuning parameters #40, #41, and #42.

  3. 3

    Verify the velocity reference is not set above the motor's rated speed.

  4. 4

    Inspect the velocity encoder for intermittent operation.

Ver todos los códigos en este manual (57)
Datos técnicos verificados. Última actualización: March 2026