937

Low read-back volts from motor armature circuit.

Otis · DSD 412 Elevator System

¿Qué significa 937 ?

This fault indicates that a low voltage read-back is detected from the motor armature circuit. This can occur during Self-Tune (Function #997) or Self-Diagnostic (Function #998).

Causas comunes

  • Missing or reversed wires connected to the armature voltage feedback at A2TB5-1 and A2TB5-2.
  • Component problem where the feedback voltage divider ratio does not match the one identified in the Cube ID PCB.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check for missing or reversed wires connected to the armature voltage feedback terminals A2TB5-1 and A2TB5-2.

Ver todos los códigos en este manual (57)