Excessive open circuit voltage to motor armature circuit.
Otis · DSD 412 Elevator System
¿Qué significa 931 ?
This fault occurs when the measured armature voltage is greater than 10% of the rated volts (parameter #7) during an open circuit test. It may occur during Self-Tune (Function #997) or Self-Diagnostic (Function #998).
Causas comunes
- Motor is rotating, generating Counter-Electromotive Force (CEMF).
- Unbalanced SCR leakage when parameter #7 (Rated Armature Volts) is set to a low value.
- Damaged SCR(s).
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Ensure the motor is not rotating during the test to prevent CEMF generation.
- 2
Temporarily increase parameter #7 (Rated Armature Volts) for the test if unbalanced SCR leakage is suspected.
- 3
Perform Self-Diagnostics (Function #998) to check for damaged SCR(s).