912
OPEN SCR FAULT
Otis · DSD 412 Elevator System
¿Qué significa 912 ?
One of the SCRs does not conduct current as expected. This condition is checked only upon request through the PCU #998 Diagnostics CDU function. The optional handheld PCDU can identify which specific SCR pair is faulty. This fault requires a DSD Power Down.
Causas comunes
- Non-conducting SCR.
- Faulty SCR gating leads.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Use the PCU #998 Diagnostics CDU function to identify the non-conducting SCR pair.
- 2
Check for faulty SCR gating leads.
- 3
Replace the faulty SCR.