RIPPLE FAULT
Otis · DSD 412 Elevator System
¿Qué significa 909 ?
Repeated high peak to average motor armature current is detected. This condition may be caused by defective hardware, poor regulator tuning, or other oscillatory operation conditions.
Causas comunes
- Defective hardware (can be discovered through PCU Diagnostics CDU function #998).
- Poor regulator tuning.
- Other oscillatory operation conditions.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Use the PCU Diagnostics CDU function #998 to check for defective hardware.
- 2
Adjust regulator tuning parameters.
- 3
Investigate and correct other oscillatory operation conditions.