907
THERMISTOR FAULT
Otis · DSD 412 DC Elevator Drive
¿Qué significa 907 ?
The thermistor used for temperature sensing is detected as either open or shorted. This fault can also occur if the ambient machine room temperature is below 0°C, causing the detected resistance to be abnormally high. On larger drives, an open thermostat will also trigger this fault. This fault will not shut down the drive.
Causas comunes
- An open circuit in the thermistor or its wiring.
- A short circuit in the thermistor or its wiring.
- Ambient machine room temperature falling below 0°C, leading to excessively high thermistor resistance readings.
- An open thermostat on larger drive models.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the thermistor and its wiring for open or short circuits; it should measure between 2K – 10K ohms at 20C room temperature.
- 2
Verify that the machine room ambient temperature is above 0°C.
- 3
On larger drives, inspect the thermostat for an open circuit.
Datos técnicos verificados. Última actualización: March 2026