Traduciendo...
401
EXCESSIVE FIELD CURRENT
Otis · DSD 412 DC Elevator Drive
¿Qué significa 401 ?
The measured motor field current exceeded 125% of the rated current, as defined by parameter #50. This can indicate issues with the motor field, current regulation, or power circuit.
Causas comunes
- Partially shorted motor field coil.
- Wrong data entry causing unstable motor field current regulator.
- Mis-wiring of module A3 (incorrect phasing).
- Wrong current tap at A3, TB4, or A3 SW1 setting.
- Malfunction of the motor field power circuit (module A3).
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the motor field coil for partial shorts.
- 2
Review and verify settings for parameters #49, #50, #51, #52, #54, and #55.
- 3
Verify that the phasing of module A3 is correct.
- 4
Verify the current tap setting at A3, TB4, or A3 SW1.
- 5
Check module A3 for malfunction within the motor field power circuit.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Otis DSD 412 DC Elevator Drive