LOOP CONTACTOR FAULT

Otis · DSD 412 DC Elevator Drive

¿Qué significa 402 ?

The Loop Contactor auxiliary contact failed to pick up or drop out within the designated time, as requested by the DSD 412 drive. The detection time is set by Function #102, which can be 450ms or 3 seconds.

Causas comunes

  • Defective Loop Contactor Auxiliary contact (check feedback at TB1-7).
  • Defective Contactor (open coil or mechanical binding).
  • Defective Pilot Relay LPR.
  • Interference from other elevator relay contact circuits.
  • Function #102 not set correctly for contactor type (e.g., small vs. large HP drives).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check for proper feedback at TB1-7 for the Loop Contactor Aux contact.

  2. 2

    Check the contactor for an open coil or mechanical binding.

  3. 3

    Check the Pilot Relay LPR for defects.

  4. 4

    Identify and resolve interference from other elevator relay contact circuits.

  5. 5

    If using large contactors with large HP drives, set Function #102 to 1 (On) for a 3-second fault detection time; otherwise, set to 0 (Off) for 450ms.