SAFETY CIRCUIT FAULT
Otis · DSD 412 DC Elevator Drive
¿Qué significa 405 ?
The Safety Circuit, wired between TB3-1 and TB3-6 on Power Supply A4, was not closed for 100 milliseconds before a “Drive Run” command, or it opened unexpectedly while the loop contactor was closed.
Causas comunes
- Safety Circuit between TB3-1 and TB3-6 not closed before a “Drive Run” command.
- Safety Circuit opened unexpectedly while the loop contactor was closed.
- Intermittent connections in the Safety Chain.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Verify that the Safety Circuit between TB3-1 and TB3-6 on Power Supply A4 is properly closed.
- 2
Check for intermittent connections in the Safety Chain.
- 3
Ensure the Safety Chain remains closed for 100ms prior to and during a “Drive Run” command.