Traduciendo...
E22

CPU Communication Error

Omron · MX2 Inverter

¿Qué significa E22 ?

This fault occurs when there is a communication failure between the two internal CPUs within the inverter. Such a failure prevents coordinated operation and leads to an inverter trip, indicating a critical internal control issue.

Causas comunes

  • Transient power disturbance or voltage ripple affecting internal CPU power rails (e.g., 5VDC or 3.3VDC).
  • Electromagnetic interference (EMI) ingress affecting internal communication buses due to poor grounding or shielding practices.
  • Hardware failure of an internal CPU component or communication bus driver chip.
  • Firmware corruption on one of the CPUs preventing proper initialization or inter-processor handshake.
  • Severe operating conditions (e.g., extreme vibration) causing internal board connection issues.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Cycle power to the inverter completely (remove main AC supply for at least 30 seconds), then reapply to reset internal CPUs.

  2. 2

    2. Verify input supply voltage (VAC) stability at the inverter terminals (R, S, T) using a multimeter; check for significant sags or surges.

  3. 3

    3. Inspect inverter grounding connections (PE terminal) for integrity and low impedance (typically <1 Ω to earth ground).

  4. 4

    4. Isolate potential sources of EMI by temporarily disabling adjacent high-frequency switching devices or ensuring proper separation of power and control wiring.

  5. 5

    5. If the error persists after power cycling, consider a firmware re-flash (if supported) or replacement of the inverter's control board.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas