2nd Multi-step Speed Reference 0 Conflicts with Jump Frequency
Omron · MX2 Inverter
¿Qué significa 285 ?
For the second motor settings, this warning indicates that the 2nd Multi-step speed reference 0 (A220) or output frequency (F001) is set to a value that falls within one of the defined 'jump frequencies' (A063/A065/A067) with its associated width (A064/A066/A068). Operating at such a speed can lead to mechanical resonance or unstable operation for the second motor at that frequency.
Causas comunes
- Parameter A220 (2nd Multi-step speed reference 0) is set to a value that falls within a configured jump frequency band (e.g., d011-d014 or similar).
- The current output frequency (F001) is attempting to operate within a forbidden jump frequency range, which is typically used to avoid mechanical resonance.
- An application-defined speed reference (A220) has been configured without considering the existing jump frequency settings (e.g., d011, d012).
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Read the current values of parameter A220 (2nd Multi-step speed reference 0) and F001 (Output frequency).
- 2
Identify all active jump frequency parameters (e.g., d011-d014 for jump frequency centers and d021-d024 for jump frequency widths) from the drive's manual.
- 3
Adjust parameter A220 to a value that is outside of any defined jump frequency bands by at least 1Hz.
- 4
Monitor F001 during operation to ensure it does not enter a jump frequency band, adjusting the speed command source if necessary.
- 5
Store the updated parameters in the drive's memory and restart the drive.