Free Setting V/f Frequency 7 Exceeds Lower Limit
Omron · MX2 Inverter
¿Qué significa 092 ?
This warning indicates that the seventh point of the free setting V/f curve (b112) is set higher than the frequency lower limit (A062). This creates an inconsistent lower boundary for the V/f characteristic, potentially restricting the minimum V/f output.
Causas comunes
- Parameter b112 (Free setting V/f curve frequency point 7) is configured with a value exceeding parameter A062 (Frequency lower limit), creating a logical inconsistency.
- The V/f curve's maximum frequency point (b112) is set above the configured minimum operational frequency (A062) for the drive.
- During parameter tuning, A062 was set to an inappropriately low value relative to the intended frequency range defined by b112.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Read the current value of parameter b112 (Free setting V/f curve frequency point 7) and parameter A062 (Frequency lower limit) from the HMI or control software.
- 2
Adjust parameter b112 to be less than or equal to the desired A062, ensuring the V/f curve point respects the frequency lower limit.
- 3
Alternatively, if a higher lower limit is intended for operation, increase parameter A062 to a value greater than or equal to b112, based on application requirements.
- 4
Store the updated parameters in the drive's memory and then perform an inverter reset to apply the changes.