Traduciendo...
#22

Function Not Allowed By Inverter State

Omron · MX2 Inverter RS-485 Connection Guide

¿Qué significa #22 ?

The Destination Device (inverter) rejected a function or write command because its current operational state or configuration prohibits the requested action. This is a protective mechanism, preventing changes that could interfere with active operations like RUN, auto-tuning, or changes to locked parameters (e.g., during Undervoltage conditions).

Causas comunes

  • Attempted to modify a register that is configured as write-protected during the inverter's RUN state.
  • Issued an 'Enter' command while the inverter was actively running.
  • Attempted to write data to a register when the inverter was in a TRIP state (e.g., Undervoltage).
  • A 'soft lock' function is enabled on the target register, preventing modification.
  • Tried to change the function of an I/O terminal that is currently allocated for a critical, unchangeable role.
  • Attempted to change the contact type of a terminal specifically allocated for the Reset (RS) function.
  • Attempted to write data to a register while the inverter's auto-tuning function was actively running.
  • Tried to write data to a password-locked register without first providing the correct password for access.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the inverter's current operating status (RUN, STOP, TRIP) before attempting to write to registers or change settings. If modification requires STOP, ensure the inverter is commanded to STOP.

  2. 2

    Check if the soft lock function is enabled for the target register and disable it if necessary before attempting to write.

  3. 3

    Enter the correct password for password-protected registers prior to attempting any write operations.

  4. 4

    Confirm that auto-tuning is not active when attempting to write to related registers. Wait for auto-tuning to complete or disable it.

  5. 5

    Review I/O terminal assignments. Do not attempt to reconfigure terminals that are fixed or allocated to critical functions like Reset (RS) during operation.

Ver todos los códigos en este manual (15)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Omron MX2 Inverter RS-485 Connection Guide