1163
RAM ERROR
Mitsubishi Electric · MELSEC System Q/L Series
¿Qué significa 1163 ?
Data in the program memory of the CPU module were overwritten. This fault occurs when an instruction is executed, indicating an integrity issue with the program memory that stores application logic.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Take noise reduction measures.
- 2
For GX Works2, select 'Transfer cache memory to program memory' in the Options dialog box.
- 3
Format the program memory, write all files to the CPU module, and run it again. If the same error code is displayed again, the cause is a hardware failure of the CPU module.